Arc flash clothing: APC 1, APC 2 and cal rating explained

Arc flash clothing is tested as APC 1 or APC 2 (box test) and with a cal rating as ELIM or ATPV (open-arc test). Read what those values mean, why you cannot convert them, and how you as an employer choose the right protection.

Sjoerd Zwarts
· bijgewerkt · 21 min lezen
Elektrotechnicus in vlamboogbeschermende werkkleding met gelaatsscherm voor een open laagspanningsverdeelkast
In dit artikel 19 onderdelen
  1. In short
  2. What is an arc flash?
  3. What is arc flash clothing?
  4. What is the difference between APC 1 and APC 2?
  5. What does the cal rating (ELIM, ATPV and EBT) mean?
  6. Which arc flash class do I need?
  7. What belongs with a complete arc flash equipment?
  8. What does an APC 1 or APC 2 set look like?
  9. Layered clothing: when does an underlayer count?
  10. Where is the class indicated on the clothing?
  11. How do you read a datasheet for arc flash PPE?
  12. How do you wash and maintain arc flash clothing?
  13. What do you do after an arc flash incident?
  14. How do you inspect and check insulating gloves and helmets?
  15. What mistakes do you often see with arc flash protection?
  16. Checklist for employers
  17. Frequently asked questions about arc flash clothing
  18. Need help choosing?
  19. Read also

Short answer

Arc flash clothing is protective clothing according to EN 61482-2 that limits the heat from an electric arc. The protection is tested in two ways: in the box test (IEC 61482-1-2) as APC 1 (4 kA) or APC 2 (7 kA), and in the open-arc test (IEC 61482-1-1) as a cal rating in cal/cm², where in Europe the ELIM is leading. APC class and cal rating cannot be converted into each other. Which class you need depends on the employer's arc flash risk assessment.

Arc flash clothing has abbreviations such as APC 2, ELIM and ATPV. What do they mean, and which one do you need?

In this article you will read how arc flash clothing is tested, how to read a label and datasheet and which parts belong to an APC 1 and APC 2 set. Want to see products right away? Check out the arc flash protection range.

In short

  • Standard: arc flash clothing falls under EN 61482-2 and is category III PPE.
  • APC 1 and APC 2: classes from the box test, at 4 kA and 7 kA.
  • Cal rating: ELIM, ATPV or EBT in cal/cm² from the open-arc test. In Europe the ELIM counts.
  • Do not convert: an APC class is not a cal value, and vice versa.
  • Closed system: jacket and trousers (or overalls) of at least the same class, without melting undergarments.
  • Choice: the class follows from the employer's arc flash risk assessment.

What is an arc flash?

An arc flash is an electric arc that occurs during a short circuit or fault in an electrical installation through the air and releases a lot of heat in a short time.

In addition to heat, an arc flash also produces:

  • Bright light
  • A bang
  • A pressure wave

The risk is mainly with work on or near energized installations, such as distribution boards and switch panels, and during switching operations.

What is arc flash clothing?

Arc flash clothing is personal protective clothing that is tested and certified according to EN 61482-2 against the thermal hazards of an electric arc.

You also know it as arc flash resistant clothing, arc flash protective clothing or arc flash clothing. The current European standard is EN 61482-2:2020: the international IEC 61482-2:2018 with European adjustments. It replaces the 2009 edition.

The standard only concerns heat. Outside the standard fall:

  • Other hazards: electric shock, sound, light and the pressure wave.
  • Other body parts: eyes, face, head, hands and feet. For that you need separate PPE.

Arc flash clothing falls under PPE category III of Regulation (EU) 2016/425, due to the high temperatures and working under voltage. A notified body inspects the type (EU-type examination) and supervises the production.

What is the difference between APC 1 and APC 2?

APC 1 and APC 2 are the two protection classes (Arc Protection Class) from the box test according to IEC 61482-1-2: APC 1 is tested at a current of 4 kA, APC 2 at 7 kA.

This is how the box test works:

  • Setup: the arc occurs in a small, enclosed box. It is intended for enclosed low-voltage installations, such as distribution boxes and switch panels.
  • Test values: 400 V AC, arc duration 500 ms, garment at a distance of 300 mm.
  • Result: pass or fail.

To pass, the fabric may, among other things:

  • not melt through to the inside;
  • not get a hole larger than 5 mm;
  • not continue to burn for longer than 5 seconds.

Also, the measured heat transfer must remain below the limit for a second-degree burn (the Stoll curve).

Until 2014, the classes were called Class 1 and Class 2. The current edition is IEC 61482-1-2:2014. View the arc flash clothing in APC 1 or the arc flash clothing in APC 2.

Diagram box test according to IEC 61482-1-2 versus open-arc test according to IEC 61482-1-1 for arc flash clothing
Box test gives a class (APC 1 or 2), the open-arc test a value in cal/cm². They cannot be converted.

APC 1, APC 2 and cal rating side by side

APC 1 APC 2 Cal rating (ELIM / ATPV / EBT)
Test standard IEC 61482-1-2 (box test) IEC 61482-1-2 (box test) IEC 61482-1-1 (open-arc test)
Test current 4 kA 7 kA 8 kA
Setup Arc in a small, enclosed box; 400 V AC, 500 ms; sample at 300 mm Same Open arc between electrodes at 300 mm; the duration of exposure is varied in a test series
Result Pass or fail Pass or fail A number in cal/cm²
On the label (EU) APC 1 APC 2 ELIM = … cal/cm² (ATPV or EBT may be added)
Convert to the other method? No No No

What does the cal rating (ELIM, ATPV and EBT) mean?

The cal rating (arc rating) is the collective name for the protection values ELIM, ATPV and EBT: the incident energy in cal/cm² that is determined in the open-arc test according to IEC 61482-1-1.

  • ELIM (incident energy limit): the energy below which in the test series no single measurement reaches the limit for a second-degree burn and the fabric does not break open. A 0% value, added in the 2019 edition.
  • ATPV (arc thermal performance value): the energy at which there is a 50% chance that the heat transfer reaches the limit for a second-degree burn.
  • EBT (energy breakopen threshold): the energy at which there is a 50% chance that the fabric breaks open.

In the European EN 61482-2:2020 only the ELIM counts for the PPE regulation. Those who follow the open-arc route must achieve at least ELIM 3.2 cal/cm² (130 kJ/m²).

On the label is the ELIM and/or the APC class; ATPV or EBT may only be added. In the United States ATPV and EBT are common. Therefore you often see only an ATPV on international datasheets.

Example: the Sioen Obera arc flash jacket has according to Sioen APC 1, ELIM 11.7 cal/cm² and ATPV 15.2 cal/cm². The same garment, three values that each say something different.

Can you convert APC to cal/cm²?

No. The box test and the open-arc test are different methods. According to the German accident insurance DGUV there is no generally valid relationship between ATPV and APC.

Many garments do have both values, for example APC 1 and an ELIM. They are then separate on the label. Jackets that have only been tested in the box test, such as the Sioen Newton, do have an APC class but no ELIM.

Note: a statement like "APC 2 is 8 cal/cm²" is not correct. There is no valid conversion between APC class and cal rating.

Does the value of the fabric apply to the whole garment?

Not automatically. The open-arc test has a test on the material and a test on the garment or the combination of layers. Seams, closures, reflective strips and layers influence the result.

A system value, for example jacket plus underlayer, only applies if the manufacturer has tested that combination as a whole. Adding separate values cannot be done: the system value can turn out higher or lower than the sum.

Which arc flash class do I need?

The required arc flash class follows from the arc flash risk assessment that the employer has carried out as part of the RI&E; a supplier cannot make that choice for you.

In the Netherlands NEN 3140, based on NEN-EN 50110-1, is the framework for safe work on low-voltage electrical installations. For high voltage that is NEN 3840. From that working method follows which tasks have an arc flash risk and what protection belongs with that.

There are two common calculation routes:

  1. Via the arc energy (kJ). In Germany, the DGUV information 203-077 describes how you calculate the expected arc energy from network data, such as the short-circuit current and the switching time. You compare that with the protection level of APC 1 or APC 2 at your working distance. This route leads to an APC class.
  2. Via the incident energy (cal/cm²). In the United States, with IEEE 1584 and NFPA 70E, the incident energy at working distance is calculated. You choose clothing with a cal rating that is at least as high. On European clothing is the ELIM, which is lower than the ATPV.

Why does the working distance count so heavily?

In the DGUV method, the protection level of an APC class grows with the square of the working distance compared to the 300 mm from the test. If you work at 600 mm instead of 300 mm, then the distance factor thus counts four times as heavily.

In addition, the DGUV calculates with a factor for the type of installation. This is a calculation rule within that method, not a conversion of APC to cal/cm². The result remains work for the one who makes the risk assessment.

Bar chart working distance in the DGUV method for arc flash: 300 mm 1x, 600 mm 4x
Calculation rule within the DGUV method, not a conversion to cal/cm².

Note: if the calculated energy comes out higher than what available PPE can handle, then heavier clothing is not the solution. According to the DGUV you then do not perform the work under voltage, or you take technical measures such as faster switching off.

What belongs with a complete arc flash equipment?

A complete arc flash equipment consists of a closed clothing system plus separate protection for face, head, hands and feet, each with its own standard.

Part Standard What do you pay attention to?
Jacket and trousers, or overalls EN 61482-2 Wear closed, from wrist and neck to ankles. Jacket and trousers both of at least the required class.
Underwear Part of the clothing system No synthetic fabrics that can melt. Choose flame-retardant underwear or natural fiber.
Face shield or arc flash hood GS-ET-29 or EN IEC 62819 Class 1 (4 kA) or class 2 (7 kA). Only valid on the helmet that the manufacturer prescribes. See also eye and face protection.
Helmet EN 397 + EN 50365 EN 50365 makes the helmet electrically insulating, but contains no arc flash requirements. View the safety helmets.
Insulating gloves EN 60903 Class 00 to 500 V AC, class 0 to 1000 V AC. Wear a leather overhand glove if the manufacturer prescribes that. View also our glove range.
Shoes EN ISO 20345 + EN 50321-1 EN 50321-1 is the standard for insulating footwear. ESD shoes are not insulating shoes.

A suit only protects if it is closed. An open jacket, rolled up sleeves or too short trousers leave spots unprotected. Choose the size therefore carefully with our size charts for arc flash clothing.

Overview complete arc flash equipment with standards for clothing, face shield, helmet, gloves and shoes
Six parts, each with its own standard or requirement.

What does an APC 1 or APC 2 set look like?

An arc flash set is a combination of clothing, face and head protection and gloves that gives all parts at least the same class.

Below are example combinations from our range. The class and cal rating per product come from the product information of the manufacturer. A combination of separate products has no own certification: each part has its own certificate and user manual.

Example set APC 1

Note: the Petzl VERTEX is electrically insulating according to EN 50365 class 0. The STRATO complies only partially with EN 50365 according to the Petzl declaration of conformity. If the helmet itself must be fully insulating, choose the VERTEX.

Do you already have a VERTEX or STRATO? Then you can order the Petzl VIZEN face shield separately.

Example set APC 2

Good to know for face and head:

  • MSA V-Gard 950 Class 2: according to MSA, electrically insulating according to EN 50365 class 0, shield tested according to GS-ET-29 class 2.
  • Kask ARC Visor Class 2: fits the Kask Zenith X (also X Max), Primero and Quantum. Kask recommends combining the visor with a balaclava.
  • Catu hood: has clips for a helmet with side slots.

Layered clothing: when does an underlayer count?

An underlayer only counts towards the protection value if the manufacturer has tested the combination as a clothing system and provides that system value; in all other cases, the value of the garment worn in that area applies.

The underlayer does matter. A synthetic fleece or thermal shirt can melt in an arc flash and worsen the burns. Therefore, only wear layers that do not melt, and preferably layers that are themselves certified according to EN 61482-2.

Examples of intermediate layers with APC 1:

Note: an APC 2 rain jacket over an APC 1 jacket does not automatically make the whole outfit APC 2. What matters is what the manufacturer has tested as a system.

Where is the class indicated on the clothing?

The arc flash class is on the CE label on the inside of the garment, next to the pictogram for arc flash protection.

According to EN 61482-2:2020, that marking consists of:

  • Pictogram IEC 60417-6353: a shield with an arc flash.
  • Standard number: the text "EN 61482-2".
  • Value: "ELIM = … cal/cm²" and/or "APC 1" or "APC 2".
  • System value: only if a combination of garments has been tested as a whole.

Pay attention to the correct symbol. The double triangle stands for working under voltage, for example on insulating gloves. It is not a sign for arc flash protection.

On a face shield according to GS-ET-29, there is a code such as 8-1-0:

  • 8: protection against a short-circuit arc flash.
  • Second digit: the class, 1 or 2.
  • Last digit: the light transmission. 0 is at least 75%, 1 is 50 to 75% and 2 is less than 50%.

The shield of the MSA V-Gard 950 Class 2 has, for example, the marking 8-2-0: class 2 with clear light transmission.

Example label for arc flash clothing with EN 61482-2, APC 1 and ELIM value in cal/cm² explained
Example, not a real product: standard, box test class and open-arc value on one label. ELIM 11.7 cal/cm² is an example value.

How do you read a datasheet for arc flash PPE?

You read a datasheet or declaration of conformity in a fixed order: standard, test method, value, system, combination conditions and certificate.

  1. Standard and edition. For clothing, that is EN 61482-2 (in Europe the 2020 version). Other standards on the same datasheet, such as EN ISO 11612 (heat and flames) or EN 1149-5 (antistatic), are additional and say nothing about arc flash.
  2. APC class. APC 1 or APC 2 comes from the box test. If only "class 2" is mentioned without a standard, ask for clarification.
  3. Cal rating. See which value is stated: ELIM, ATPV or EBT. Compare products only on the same value. The Sioen Urbino gives, for example, ELIM 16 and EBT 19 cal/cm², the Obera ELIM 11.7 and ATPV 15.2 cal/cm².
  4. Garment or system. If a system value is stated, check which layers the combination was tested with.
  5. Combination conditions. For shields, it states which helmets are allowed. For some gloves, the arc flash class only applies with a certain leather overhand, such as with the Ansell RIG014.
  6. Certificate. For PPE category III, it states the number of the notified body that performed the EU type examination. You can look up that number in the European NANDO database.

How do you wash and maintain arc flash clothing?

You wash and maintain arc flash clothing according to the label and the manufacturer's instructions; deviating from this can affect the protection.

  • No detergent additives: no chlorine bleach, hydrogen peroxide, fabric softener, starch or dryer sheets.
  • Contamination: oil and grease can ignite in an arc flash. If contamination does not come out, replace the garment.
  • Inspection: check the clothing before every use. Damaged or contaminated means: do not use.
  • Repair: only with the same arc flash-resistant material and flame-retardant thread, according to the manufacturer.

What do you do after an arc flash incident?

After an arc flash incident, take the affected arc flash clothing out of use and replace it, even if you do not see any damage.

  1. Replace clothing. Manufacturers state that clothing should not be reused after exposure to an arc flash, because material degradation is not always visible. Repair is not an option.
  2. Check other PPE. Follow the manufacturer's instructions for the helmet, shield and gloves.
  3. Review risk analysis. Check with the employer whether the risk analysis and the chosen class are still correct.

How do you inspect and check insulating gloves and helmets?

You check insulating gloves before every use with an air test and a visual inspection; you use an insulating helmet according to EN 50365:2024 for a maximum of 5 years from the date of first use.

  • Gloves class 00 and 0 (up to 500 V and 1000 V AC): inflate and check for leaks and damage before every use. Whether and how often they are electrically retested afterwards is stated in the manufacturer's instructions. The German DGUV rule 103-011 does not provide for a fixed periodic electrical retest for these two classes.
  • Gloves class 1 to 4 (higher voltages): these are periodically electrically retested. Manufacturers state a period of maximum 6 months.
  • Insulating helmets: EN 50365:2024 requires the date of first use to be noted on the helmet and has a field for retest dates. After 5 years, the helmet is taken out of use.
Hands with insulating rubber gloves and leather overhands operating a switch in a distribution board
Insulating gloves with leather overhands for protection (lifestyle image).

You can find more protective equipment for electrical work in our PPE range.

What mistakes do you often see with arc flash protection?

  • Only an arc flash jacket. An APC 2 jacket with ordinary work trousers does not protect the legs against an arc flash.
  • Mistaking flame retardant for arc flash resistant. EN ISO 11612 is not an arc flash test; EN 61482-2 is required for that.
  • Using a partially insulating helmet as fully insulating. Read whether a helmet meets EN 50365 fully or partially.
  • Using ESD or antistatic shoes as insulating shoes. Insulating footwear falls under EN 50321-1.
  • Non-existent standard years. The 2014 edition of IEC 61482-1-2 is valid. If a document mentions another edition, ask for the certificate.

Checklist for employers

  • Have an arc flash risk analysis carried out as part of the RI&E and determine the required APC class or cal value per task.
  • Choose clothing according to EN 61482-2 with the APC class and/or ELIM on the label that matches that result.
  • Provide a complete outfit: jacket and trousers, or overalls, of at least the same class.
  • Ensure non-melting underclothing.
  • Complete the set with a face shield or arc flash hood (GS-ET-29 or EN IEC 62819) on the prescribed helmet, insulating gloves (EN 60903), with an overhand according to the manufacturer, and where necessary, insulating footwear.
  • Keep the EU declaration of conformity and the Dutch instructions for use for each product.
  • Have insulating gloves class 00 and 0 checked with an air test before every use.
  • Note the date of first use on insulating helmets.
  • Do not have anything changed on the clothing, such as shortening, repairing or printing, without the manufacturer's approval.
  • Replace clothing after an arc flash incident.

Note: this article provides general explanation about standards and markings and does not replace an arc flash risk analysis. What protection is needed follows from the RI&E and the employer's risk analysis. Always follow the manufacturer's instructions and certificate.

Frequently asked questions about arc flash clothing

Why is the ELIM lower than the ATPV?

ATPV and EBT are 50%-values: at that energy there is a 50% chance in the test of a second-degree burn or of the fabric opening. The ELIM is the level below which in the entire test series not a single measurement reaches the burn limit and the fabric does not open. Therefore, the ELIM of the same garment is by definition lower. So never compare the ELIM of one product with the ATPV of another.

What does an NFPA 70E category mean and does it apply in the Netherlands?

NFPA 70E is an American standard. The PPE categories 1 to 4 belong there to a minimum arc rating of 4, 8, 25 and 40 cal/cm². In Europe, EN 61482-2 is the standard for arc flash clothing, with the APC class and/or the ELIM on the label. There is no official table that links APC 1 or APC 2 to an NFPA category.

What does 'class 1' mean for arc flash PPE?

That depends on the standard. Class 1 can stand for APC 1 for clothing (IEC 61482-1-2), class 1 for a face shield (GS-ET-29), an NFPA category, or a voltage class for insulating gloves (EN 60903) or helmets (EN 50365). Therefore, always look at the standard and the class together, for example EN 61482-2 with APC 1.

Does an insulating helmet or glove also protect against an arc flash?

Not by itself. EN 50365 for electrically insulating helmets contains no arc flash requirements, and EN 60903 for insulating gloves is about protection against an electric shock. A glove only protects against an arc flash if the manufacturer has tested it for that separately, for example with an APC class.

Can you put an arc flash face shield on every helmet?

No. A face shield according to GS-ET-29 is tested and certified in combination with the helmet the manufacturer specifies. With another helmet type you fall outside that certification. In the instructions for use of the shield it states which helmets are allowed.

How long can you use an electrically insulating helmet?

According to EN 50365:2024 a maximum of 5 years from the date of first use, which you note on the helmet. The standard has class 00 (500 V AC), 0 (1000 V AC), 1 (7500 V AC) and 2 (17000 V AC). These classes say nothing about arc flash protection; for that you look at the face shield or the arc flash hood.

Which documents belong with arc flash clothing?

Arc flash clothing is PPE of category III under Regulation (EU) 2016/425. The manufacturer provides an EU declaration of conformity or states in the instructions for use where it is available online. The usage information must be in a language the user understands; in the Netherlands that is Dutch. Keep these documents in your PPE administration.

Need help choosing?

Do you want to equip a whole team or are you unsure which parts fit together? Send us the quantities, the sizes and the class from your risk analysis. We will put together a suitable set; you determine the class based on that analysis.

About the author

Sjoerd Zwarts is the manager of Hef en Hijs Online, the webshop for certified lifting and hoisting equipment, fall protection and personal protective equipment. Together with sister company Zwarts Veiligheid & Techniek he works towards one goal: that everyone who lifts, hoists or works on installations goes home safely at the end of the day. In his articles he translates standards and certificates into clear choices for practice.